Brand Name : Chuangyin
Model Number : LSZ107 8
Certification : Type Test Report
Place of Origin : China
MOQ : 1
Price : negotiable
Payment Terms : T/T, L/C, Western Union, MoneyGram, D/P, D/A,
Supply Ability : 1000pcs/week
Delivery Time : Within 7 days
Packaging Details : Carton packing for one sets, one set including three piece with Components
Application : For GIS
Technical Data : IEC 60044-1/ IEC 61869-1&2
Features : Bottom Has Installation Inserts for Fixation
Power Frequency Witnstand Voltage : 3kv
Rated Frequency : 50/60HZ
Package : 3pcs/Plywood415*235*405mm
LSZ Instrument Current Transformer, Three Phase Rated Secondary Current 5A,1A
The three-phase CT is full-enclosed in the flame retardant plastic shells, primary bushing or cable can pass through the Inner hole, bottom has Installation Inserts for fixation. It Is simple and shortcut, Is suitable for measuring current, signal collection and protective relaying In the medium voltage power system of bushing or cable etc.
Purpose | Measuring current transformer | Protective current transformer | Double winding current transformer | ||||||
Rated Transformation Ratio | Accuracy class and rated burden (VA) cos =0.8 | ||||||||
0.5 | 1 | 10P10 | 0.5 | 10P1010P5 | |||||
150/5 | 1 | 1 | |||||||
200/5 | 1 | 2.5 | 1.5 | 1.5 | 1.5 | ||||
300/5 | 2.5 | 5 | 2.5 | 1 | 2.5 | ||||
400/5 | 5 | 7.5 | 5 | 2.5 | 2.5 | ||||
500/5 | 5 | 7.5 | 5 | 2.5 | 5 | ||||
600/5 | 5 | 7.5 | 5 | 5 | 5 |
![]() |